Friday, April 30, 2010

Comment stsetch2 SNF 2010-04-30 13:38:13: Update turbo

Flushed out the turbo cooling water line. Before the flush, the inlet water temperature (according to the turbo controller) was 48 C. After the flush, the temp = 24 C. I' ve run been running process for about 2.5 hours with no turbo failure. Bearing temp has risen about 3 C to 61 C. Will continue to monitor.

No comments: